The
material cast iron
The material used for Düker cast iron sewage pipes and fittings
corresponds to the regulations of DIN EN 877 with the following
characteristics:
| Density: |
Approx. 7.2 kg/dm³
(71.5 KN/m³) |
 |
| Minimum tensile
strength: |
150 MPa for fittings,
200 MPa for pipes |
 |
| Compressive strength: |
Approx. 3 to 4 times
the value of the minimum tensile strength |
 |
| Shearing strength: |
1.1 to 1.6 times the
value of the minimum tensile strength |
 |
| Crushing
strength: |
350 MPa
(for DN < 250)
or 332 MPa (for DN = 250 or more) |
 |
| Poisson’s number: |
0,3 |
 |
| Coefficient of length
expansion: |
0.0105 mm/mK (between
0º and 100 ºC) |
 |
| Thermal conduction
coefficient: |
50 - 60 W/mK (at 20 ºC) |
 |
| Modulus of elasticity: |
8 x 104 to 12 x 104
N/mm² |
Coating
technologies:
Coatings protect and finish cast iron sewage pipes and fittings.
Coating technologies distinguish a manufacturer for his know-how and
experience.
|